▇ PID Change action ON/OFF
1.Press and hold "MODE" key 5 sec to enter LEVEL 2
2.Set "P-1=0" (open ON/OFF)
(OFF: PV>SV+HYS1)
(ON : PV<SV-HYS1)
3. Set deadband range HYS1=5
(P-1=0, will be displayed HYS1)
Annotations:
P-1 default =3.0
The first group of proportion with the time
Range:0-200.0%
HYS1 Default value = 1.0
PS: Parameter【P-1】=0, will automatically turn off