https://www.kce.url.tw/en/custom_14676.html 2.Parameter(P-1、HYS1) PID Change action ON/OFF 2.Parameter(P-1、HYS1) PID Change action ON/OFF ▇ PID Change action ON/OFF    1.Press and hold "MODE" key 5 sec to enter  LEVEL 2 2.Set "P-1=0" (open ON/OFF)    (OFF: PV>SV+HYS1)  (ON : PV<SV-HYS1) 3. Set deadband range HYS1=5     (P-1=0, will be displayed HYS1)    Annotations: P-1 default =3.0 The first group of proportion with the time Range:0-200.0% HYS1 Default value = 1.0   PS: Parameter【P-1】=0, will automatically turn off     【AT】automatic calculation
https://www.kce.url.tw/en/ KE CHYUN ELECTRIC CO., LTD

▇ PID Change action ON/OFF 


 

1.Press and hold "MODE" key 5 sec to enter  LEVEL 2

2.Set "P-1=0" (open ON/OFF)

   (OFF: PV>SV+HYS1)

 (ON : PV<SV-HYS1)

3. Set deadband range HYS1=5

    (P-1=0, will be displayed HYS1)

  

Annotations:

P-1 default =3.0

The first group of proportion with the time

Range:0-200.0%

HYS1 Default value = 1.0

 

PS: ParameterP-1=0, will automatically turn off

    ATautomatic calculation