▇ INPT: AN5 from 0-100.0 change 0-9999
Note: Enter the K type, PT100 (thermocouple)
decimal point position adjustment, please also refer to
Thermocouple decimal point position【INPT: K2 change K3】
1. Press and hold "MODE" key 5 sec to enter LEVEL 2
2. Set "Lock=1111"
3. Press and hold "MODE" key + "<" key 5 sec to enter LEVEL 4
4. Set "St-2-2=1"
(Default 0100 was revised to 0110)
5. Press AUT key Back to LEVEL1
(Press and hold" MODE" key for 5 Back to LEVEL1)
6. Press and hold "MODE" key + "<" key 5 sec to enter LEVEL 3
7. Move the decimal point position setting dp
8. Seetting range high point "PVHI=9999"