https://www.kce.url.tw/en/custom_15142.html  06. ( DP ) AN1~5 decimal point position  06. ( DP ) AN1~5 decimal point position ▇ INPT: AN5  from  0-100.0 change 0-9999   Note: Enter the K type, PT100 (thermocouple)          decimal point position adjustment, please also refer to          Thermocouple decimal point position【INPT: K2 change K3】 1. Press and hold "MODE" key  5 sec to enter  LEVEL 2 2. Set "Lock=1111" 3. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 4 4. Set "St-2-2=1"  (Default 0100 was revised to 0110) 5. Press AUT key Back to LEVEL1 (Press and hold" MODE" key for 5 Back to LEVEL1) 6. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 3 7. Move the decimal point position setting dp 8. Seetting range high point "PVHI=9999"  
https://www.kce.url.tw/en/ KE CHYUN ELECTRIC CO., LTD

▇ INPT: AN5  from  0-100.0 change 0-9999


 

Note: Enter the K type, PT100 (thermocouple)
         decimal point position adjustment, please also refer to
         Thermocouple decimal point position【INPT: K2 change K3】


1. Press and hold "MODE" key  5 sec to enter  LEVEL 2

2. Set "Lock=1111"

3. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 4

4. Set "St-2-2=1" 

(Default 0100 was revised to 0110)

5. Press AUT key Back to LEVEL1

(Press and hold" MODE" key for 5 Back to LEVEL1)

6. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 3

7. Move the decimal point position setting dp

8. Seetting range high point "PVHI=9999"