▇ Digital Filter / adjust the PV display response rate 【FILT】
1. Press and hold "MODE' key 5 sec to enter LEVEL 2
2. Set"LocK"=1111
3. Press and hold "MODE" key + "<" key 5 sec to enter LEVEL 4
4. Set"St-6-4=1"
(Default 0100 was revised to 0110)
5. Press AUT key Back to LEVEL1
(Press and hold "MODE" key for 5 Back to LEVEL1)
6. Press and hold "MODE" key + "<" key 5 sec to enter LEVEL 3
7. Set "FILT" PV value adjustment shows the reaction rate
Note: range 0-5000