Custom Page

▇ AN1~5 Input high / low compensation


1. Press and hold "MODE" key  5 sec to enter  LEVEL 2

2. Set "Lock=1111"

3. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 4

4. Set "St-2-2=1" 

(Default 0100 was revised to 0110)

5. Press AUT key Back to LEVEL1

(Press and hold "MODE' key for 5 Back to LEVEL1)

6. Press and hold "MODE' key + "<" key 5 sec to enter  LEVEL 3

7. Set InLo, InHi adjust the input bias

 

【4-20mA】  INLO About 20        INHI About 5250

【0-10V】     INLO About -140     INHI About 5700

【0-1V】       INLO About -120     INHI About 5200

【10-50mV】INLO About -1230   INHI About 7747

【1-5V】       INLO About -240     INHI About 4164