▇ AN1~5 Input high / low compensation
1. Press and hold "MODE" key 5 sec to enter LEVEL 2
2. Set "Lock=1111"
3. Press and hold "MODE" key + "<" key 5 sec to enter LEVEL 4
4. Set "St-2-2=1"
(Default 0100 was revised to 0110)
5. Press AUT key Back to LEVEL1
(Press and hold "MODE' key for 5 Back to LEVEL1)
6. Press and hold "MODE' key + "<" key 5 sec to enter LEVEL 3
7. Set InLo, InHi adjust the input bias
【4-20mA】 INLO About 20 INHI About 5250
【0-10V】 INLO About -140 INHI About 5700
【0-1V】 INLO About -120 INHI About 5200
【10-50mV】INLO About -1230 INHI About 7747
【1-5V】 INLO About -240 INHI About 4164