Custom Page

▇ 【SVOS】SV value compensation


 

1. Press and hold "MODE" key 5 sec to enter  LEVEL 2

2. Set "P-1=0" (ON/OFF)

  (OFF: PV>SV+HYS1)

  (ON : PV<SV-HYS1)

3. Set "HYS1=1"

  (P-1=0 display when HYS1)

4. Press AUT key Back to LEVEL1

(Press and hold "MODE" key for 5 Back to LEVEL1)

5. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 3

6. Set "SVOS=+5"

 

PV > SV + HYS1 + SVOS

PV > SV +  1    +   5      Close Output

 

PV < SV - HYS1 + SVOS

PV < SV -   1     +    5    Close Output

 

Note: Parameter [P-1] description link