https://www.kce.url.tw/en/custom_19378.html 5.Parameter(LO01,HI01)output highs,lows correction 5.Parameter(LO01,HI01)output highs,lows correction ▇ Output highs、lows correction 1. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 3 2. (PV 3. (PV>SV Close Output) Calibration LO01 calibration output low point deviation     < Repeated calibration, verification accuracy>   Parameter【LO02、HI02】calibration the second set of outputs Correction mode and 【LO01, HI01】 same  
https://www.kce.url.tw/en/ KE CHYUN ELECTRIC CO., LTD

▇ Output highs、lows correction



1. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 3

2. (PV

3. (PV>SV Close Output) Calibration LO01 calibration output low point deviation

    < Repeated calibration, verification accuracy>

 

ParameterLO02HI02calibration the second set of outputs

Correction mode and LO01, HI01 same