https://www.kce.url.tw/en/custom_19583.html 7. Parameter (R-Y) Hot runner/Preheat function 7. Parameter (R-Y) Hot runner/Preheat function ▇ Parameter【R-Y、W-T】hot runner/preheat function   1. Press and hold "MODE" key 5 sec to enter  LEVEL 2 2. Set "Lock=1111" 3. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 4 4. Set "St-5-3=1" (Default 0000 was revised to 0100) 5. Press AUT key Back to LEVEL1 (Press and hold" MODE" key for 5 Back to LEVEL1) 6. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 3 7. Set "r-Y=105" (reheating temperature) 8. Set "W-t=40" (preheat output limit the proportion of)   Parameter W-t in programmable the use of wait function  9. Press AUT key Back to LEVEL1 (Press and hold" MODE" key for 5 Back to LEVEL1) 10. SV>PV when turned on output 11. Temperature does not exceed 105 degrees when the output limit of 40%       Temperature over 105 when open normally output Temperature exceeds r-Y set value 0.1 degrees  turn on automatic calculation
https://www.kce.url.tw/en/ KE CHYUN ELECTRIC CO., LTD

▇ Parameter【R-Y、W-T】hot runner/preheat function


 

1. Press and hold "MODE" key 5 sec to enter  LEVEL 2

2. Set "Lock=1111"

3. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 4

4. Set "St-5-3=1"

(Default 0000 was revised to 0100)

5. Press AUT key Back to LEVEL1

(Press and hold" MODE" key for 5 Back to LEVEL1)

6. Press and hold "MODE" key + "<" key 5 sec to enter  LEVEL 3

7. Set "r-Y=105" (reheating temperature)

8. Set "W-t=40" (preheat output limit the proportion of)

  Parameter W-t in programmable the use of wait function 

9. Press AUT key Back to LEVEL1

(Press and hold" MODE" key for 5 Back to LEVEL1)

10. SV>PV when turned on output

11. Temperature does not exceed 105 degrees when the output limit of 40%

      Temperature over 105 when open normally output

Temperature exceeds r-Y set value 0.1 degrees 

turn on automatic calculation