https://www.kce.url.tw/en/custom_19875.html 9. Optional features-Remove SV 9. Optional features-Remove SV ▇ Remove SV      1. Press MODE key for 5 sec to enter LEVEL PID 2. Set "LocK=1111" 3. Press and hold MODE key +"<"key to enter the LEVEL 4 4. Set "St-2=1110" 5. Set "INP2=1" 6. Press AUT key Back to LEVEL1     (Press and hold MODE key for 5 Back to LEVEL1) 7. Hold the MODE key + "<" into the third layer 8. Use corrector / correction input signal highs, lows value     2nHi = 20mA = about 4189     2nLo =  4mA = about -78   
https://www.kce.url.tw/en/ KE CHYUN ELECTRIC CO., LTD

▇ Remove SV

 

  

1. Press MODE key for 5 sec to enter LEVEL PID

2. Set "LocK=1111"

3. Press and hold MODE key +"<"key to enter the LEVEL 4

4. Set "St-2=1110"

5. Set "INP2=1"

6. Press AUT key Back to LEVEL1

    (Press and hold MODE key for 5 Back to LEVEL1)

7. Hold the MODE key + "<" into the third layer

8. Use corrector / correction input signal highs, lows value

    2nHi = 20mA = about 4189

    2nLo =  4mA = about -78