▇  HP - High Point Compensation (No decimal point) PT100

 

1. Hold "SET" key 5sec to enter LEVEL 1

2. Set HP adjustment High Point Compensation

    (HP=5
    When the temperature is increased to 100 degrees
    show an increase of 100 + 5 degrees
    When the temperature is increased to 200 degrees
    show an increase of 200 + 10 degrees
    When the temperature is increased to 300 degrees
    show an increase of 300 + 15 degrees
    and so forth...)

 

▇  HP - High Point Compensation (a decimal point) 4-20 mA

 

 

1. Hold "SET" key 5sec to enter LEVEL 1

2. PV increases 5%
    PV increases 10%

3. Input  4    mA = 0
    Input  8    mA = 26.1
    Input  12  mA = 52.4
    Input  16  mA = 78.6
    Input  20  mA = 105.0

 

 

 ▇  LP - Low compensation (No decimal point) PT100


 

1. Hold "SET" key 5sec to enter LEVEL 1

2. Set LP adjustment Low Point Compensation

    (HP=5
    When the temperature is increased to 100 degrees
    show an increase of 100 + 5 degrees
    When the temperature is increased to 200 degrees
    show an increase of 200 + 5 degrees
    When the temperature is increased to 300 degrees
    show an increase of 300 + 5 degrees
    and so forth...)

 

 ▇  LP - Low compensation (a decimal point) 4-20mA

 
 

  

1. Hold "SET" key 5sec to enter LEVEL 1

2. Set LP adjust the low compensation,
    let the temperature increase of 5 degrees

3. Input  4    mA = 5
    Input  8    mA = 29.9
    Input  12  mA = 54.9
    Input  16  mA = 79.9
    Input  20  mA = 104.9