KCR-616 channel paperless recorder
▇ Description
It is the Low Cost paperless recorder in bigger size 6.4" with highest resolution 640x480 pixels VGA TFT display, infrared detector, maximum 6 channels, plug & play I/O cards. It has many other unique features too, 12 soft keys for easy operation, universal input, the shortest depth 174mm, well designed portable handle, fully isolated channels, reliable and high capacity storage media CF card.
As a professional and experienced manufacturer, we supply high-performance and quality paperless recorders, video graphic recorders, paperless chart recorders, chart recorders, and temperature chart recorders.
▇ Features
6.4"Color TFT LCD with 640X480 pixels resolution
The Maximum Channels :
6 isolated analog input channels
Plug & Play Supported I / O card, 6 Slots
The High Flexibility :
User configurable l / O card
Expandable modular architecture
Flexible screen configuration
User-Friendly
Soft keys coupled with interactive dialog simplify
setup & operation procedures
Easy - to - access function keys
Infrared Detector:
Shut off LCD automatically to prolong LCD life
and save power while nobody near by
Save Space:
Only 174 mm (6.9") depth behind panel
Various Display Formats:
Vertical trend , Horizontal trend,
Bar Graph, Numerical or mixed
Save Data in Flash ROM,
Compact Flash Card or PC
Communication :
Standard Ethernet and optional RS-232 / 422 / 485
The Highest Accuracy
18 - bit A -D analog input, 15-bit D-A analog output.
Fast Sampling Rate:
Within 200 msec for all channels,
Programmable Filter or Moving Average Sampling Method
Statistics with Instant , Average , Min./ Max. Values
Progammable Alarms and Messages available
Portable / Bench Top Assembly Kit available
Specification | |
Hardware | |
Power | 90-250VAC, 47-63Hz, 60VA, 30W maximum 11-18VDC or 18-36 VDC, 60VA, 30W maximum |
Display | 6.4〞TFT LCD, 640X480 pixel resolution, 256 colors |
Memory | 8MB storage memory on board Storage media: 128, 512 MB, 1 GB CF (Compact Flash) cards |
Analog Input Cards (AI181, AI182, AI183) | |
Channels | AI181 ~ 1 channel, AI182 ~ 2 channels, AI183 ~ 3 channels |
Resolution | 18 bits |
Sampling Rate | 5 times/ second |
Maximum Rating | -2 VDC minimum, 12 VDC maximum (1 minute for mA input) |
Temperature Effect | ±1.5 μV/ μC for all inputs except mA ±3.0 μV/ μC for mA input |
Sensor Lead Resistance Effect | T/C: 0.2 μV/ohm 3-wire RTD: 2.6 μC /ohm of resistance difference of two leads 2-wire RTD: 2.6 μC /ohm of resistance sum of two leads |
Burn-out Current | 200nA |
Common Mode Rejection Ratio (CMRR) | 120dB |
Normal Mode Rejection Ratio (NMRR) | 55dB |
Isolation Breakdown Voltage between channels | 430VAC min. |
Sensor Break Detection | Sensor opened for TC, RTD and mV inputs, below 1 mA for 4-20mA input, below 0.25V for 1-5V inputs, unavailable for other inputs. |
Sensor Break Responding Time | Within 10 seconds for TC, RTD and mV inputs, 0.1 second for 4-20 mA and 1-5V inputs. |
Characteristics: |
|||
Type | Range | Accuracy@ 25 °C | Input Impedance |
J | -120 ~ 1000 °C (-184 ~ 1832 °F) |
±1 °C | 2.2MΩ |
K | -200 ~ 1370 °C (-328 ~ 2498°F) |
±1 °C | 2.2MΩ |
T | -250 ~ 400°C (-418 ~ 752°F) |
±1 °C | 2.2MΩ |
E | -100 ~ 900 °C (-148 ~ 1652 °F) |
±1°C | 2.2MΩ |
B | 0 ~ 1820 °C (32 ~ 3308 °F) |
±2°C | 2.2MΩ |
R | 0 ~ 1768 °C (32 ~ 3214 °F) |
±2°C | 2.2MΩ |
S | 0 ~ 1768 °C (32 ~ 3214 °F) |
±2°C | 2.2MΩ |
N | -250 ~ 1300 °C (-418 ~ 2372 °F) |
±1 °C | 2.2MΩ |
L | -200 ~ 900 °C (-328 ~ 1652 °F) |
±1 °C | 2.2MΩ |
PT100 (DIN) |
-210 ~ 700 °C (-346 ~ 1292 °F) |
±0.4°C | 1.3KΩ |
PT100 (JIS) |
-200 ~ 600 °C (-328 ~ 1112 °F) |
±0.4°C | 1.3KΩ |
mV | -8 ~ 70mV | ±0.05% | 2.2MΩ |
mA | -3 ~ 27mA | ±0.05% | 70.5Ω |
0~1V | -0.12 ~ 1.15V | ±0.05% | 32KΩ |
0~5V | -1.3 ~ 11.5V | ±0.05% | 332KΩ |
1~5V | -1.3 ~ 11.5V | ±0.05% | 332KΩ |
0~10V | -1.3 ~ 11.5V | ±0.05% | 332KΩ |
Analog Input Cards (AI183V): |
|||
Type | Range | Accuracy@ 25 °C | Input Impedance |
-60~60mV | -62~62mV | ±0.1% | 2.2 MΩ |
-2~2V | -2.2~2.2V | ±0.3% | 332KΩ |
-20~20 V | -22~22 V | ±0.1% | 332KΩ |
-20~20 mA | -22~22 mA | ±0.1% | 70.5Ω |
Digital Input Card (DI181) | |
Channels | 6 per card Logic |
Low | -5V minimum, 0.8V maximum |
Logic High | 2V minimum, 5V maximum |
External pull-down Resistance | 1KΩ maximum |
External pull-up Resistance | 1.5MΩ minimum |
Digital Output Card (DO181) | |
Channels | 6 per card |
Contact Form | N.O.(Form A) |
Relay Rating | 5A/240 VAC, life cycles 200,000 for resistive load |
Analog Output Card (AO183I, AO183V) | |
Channels | 3 per card Output signal: AO183I: 4-20mA, 0-20mA, AO183V: 0-5V, 1-5V, 0-10V |
Resolution | 15 bits |
Accuracy | ±0.05% of Span ±0.0025% /°C |
Load Resistance | 0-500 ohms (current), 10K ohms minimum (voltage) |
Output Regulation | 0.01% for full load change |
Output Setting Time | 0.1 second (stable to 99.9%) |
Isolation Breakdown Voltage | 1000VAC min. |
Integral Linearity Error | ±0.005% of Span |
Temperature Effect | ±0.0025% of Span /°C |
24VDC Auxiliary Power Supply Card (AP181) | |
Channels | to be used for 6 transmitters |
Output Rating | 24 ± 1 VDC, 180mA in maximum, 30mA / each channel |
COMM Module (CM181) | |
Interface | RS-232 (1 unit), RS-485 or RS-422 (up to 247 units) |
Protocol | Modbus Protocol RTU mode |
Address | 1-247 |
Baud Rate | 0.3 - 38.4Kbits / sec |
Measured data Bits | 7-8 bits |
Parity Bit | None, Even or Odd |
Stop Bit | 1 or 2 bits |
Standard Ethernet Communication | |
Protocol | Modbus TCP/IP, 10 Base T |
Ports | AUI (Attachment Unit Interface) and RJ-45, Auto- detect capability |
Infrared Detector | |
Distance | Detect moving human body in distance around 2 meters |
Time delayed | 10, 20, 30, 40, 50 or 60 minutes to be defined |
Real time clock accuracy vs. temperature inside of housing | |
Temperature inside housing typical error per month | 10 ~ 40 °C 18 seconds 0 °C or 50 °C 52 seconds -10°C or 60 °C 107 seconds |
Environmental & Physical | |
Operating Temperature | 5 ~ 50 °C |
Storage Temperature | -25 ~ 60 °C |
Humidity | 20 to 80% RH (non-condensing), maximum relative humidity 80% for temperature up to 31°C decreasing linearly to 50% relative humidity at 40°C |
Altitude | 2000 M maximum |
Insulation Resistance | 20 M ohms min. (at 500 VDC) |
Dielectric Strength | 1350 VAC, 50/60 Hz for 1 minute |
Vibration Resistance | 10-55 Hz, 10m/ s2 for 2 hours |
Shock Resistance | 30m/ s2 (3g) for operation, 100g for transportation |
Operation Position | no inclined restriction |
Dimensions | Panel Mount style: 166(W) x 144(H) x 174mm(D) |
Bench Top style | 166 (W) x 192 (H) x 194mm (D) |
Standard Panel Cutout | DIN size in 138 x 138mm |
Approval Standards | |
Safety | UL61010C-1, CSA C22.2 No. 24-93 |
CE | EN61010-1 (IEC1010-1) over voltage category II, Pollution degree 2 |
Protective Class | IP 30 front panel for indoor use, IP 20 housing and terminals |
EMC | Emission: EN61326 (EN55022 class A, EN61000-3-2, EN61000-3-3) Immunity: EN61326 (EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11) |
Ordering Code | |||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||
1 Power | 4: 90-250 VAC, 47-63 Hz 5: 20-28 VAC, 47-63 Hz 6: 11-18 VDC 7: 18-36 VDC 8. 36-72 VDC 9: Special order |
||||||||||||||||||||||||||
2 Analog Input Card | 0: none 1: 1 channel withAI181 G: 3 channels with AI183V 2: 2 channels with AI182 H: 6 channels with AI183V 3: 3 channels with AI183 J: 9 channels with AI183V 4: 4 channels with AI181 & AI183 K: 12 channels with AI183V 5: 5 channels with AI182 & AI183 L: 15 channels with AI183V 6: 6 channels with AI183 M: 18 channels with AI183V A: 9 channels with AI183 B: 12 channels with AI183 C: 15 channels with AI183 D: 18 channels with AI183 *See AI181/2/3(V) in Accessories below. |
||||||||||||||||||||||||||
3 Digital Input Card | 0: none 1: 6 channels 4: 24 channels 2: 12 channels 5: 30 channels 3: 18 channels 6: 36 channels |
||||||||||||||||||||||||||
4 Digital Output Card | 0: none 1: 6 relays 3: 18 relays 2: 12 relays 4: 24 relays |
||||||||||||||||||||||||||
5 Communication | 0: standard Ethernet interface 1: RS-232/422/485 ( three in one ) + Ethernet interface 9: special order |
||||||||||||||||||||||||||
6 PC software | 1: Free basic software Observer I for non-communication application 2: Extensive software Observer II for communication of RS-232/422/485 or Ethernet |
||||||||||||||||||||||||||
7 Firmware | 0: Basic function 1: with Mathematics, Counter & Totalizer & FDA 21 CFR part 11 compliance |
||||||||||||||||||||||||||
8 Storage Media | 1. 512 MB Compact Flash card 6: 1 GB Compact Flash card X: other options |
||||||||||||||||||||||||||
9 Case/Mounting | 1: standard panel mounting, grey case 2: Bench top / portable style with handle, USA power cable, grey case 3: Bench top with handle, European power cable, grey case |
||||||||||||||||||||||||||
10 Special Option | 0: none 1: 24VDC auxiliary power supply ( for transmitter, 6 channels ) 2: 3-channel current output 3: 6-channel current output 4: 9-channel current output D: 3-channel voltage output E: 6-channel voltage output F: 9-channel voltage output 5: panel mounting with rear power plug 6: panel mounting with front power switch 7: 7=1+5 8: 8=1+6 9: 9=1+5+6 X: other options |